On Load Loss of the Transformer VS No Load Loss of the Transformer

Views: 324     Author: Site Editor     Publish Time: 2026-07-24      Origin: Site

Inquire

wechat sharing button
facebook sharing button
linkedin sharing button
whatsapp sharing button
sharethis sharing button

Every power transformer, regardless of its size, type, or application, experiences energy losses during operation. These losses are not merely a theoretical concern — they determine the transformer's operating cost, thermal performance, service life, and environmental impact over decades of continuous service. Transformer losses fall into two fundamental categories: no load loss (also called core loss or iron loss) and on load loss (also called load loss, copper loss, or winding loss). Understanding the difference between these two loss mechanisms is essential for anyone involved in transformer specification, procurement, operation, or energy management.

On Load Loss No Load Loss .webp

What Is No Load Loss?

No load loss is the power consumed by a transformer whenever it is energized, regardless of whether it is supplying any load. Even when the secondary terminals are open-circuited and no current flows to any connected equipment, the transformer draws a small but continuous amount of power from the supply. This standby consumption persists 24 hours a day, 365 days a year, for as long as the transformer remains connected to the grid.

No load loss occurs primarily in the transformer's magnetic core and consists of three components: hysteresis loss, eddy current loss, and minor stray loss. Hysteresis loss arises from the energy required to repeatedly magnetize and demagnetize the core material as the alternating magnetic flux reverses direction 100 or 120 times per second (at 50 Hz or 60 Hz). Each magnetic cycle dissipates a small amount of energy as heat within the core steel. Eddy current loss is caused by circulating currents induced within the core material itself by the changing magnetic flux. These currents flow through the electrical resistance of the steel, producing I²R heating. Stray loss accounts for a small additional contribution from leakage flux that intercepts the transformer tank, clamping structures, and other metallic components.

The key characteristic of no load loss is that it is constant — it does not vary with the load on the transformer. Whether the transformer is supplying zero load or full rated load, the no load loss remains essentially the same. It is also strongly dependent on the square of the applied voltage, meaning that even modest overvoltage conditions significantly increase core losses.

What Is On Load Loss?

On load loss — also referred to as load loss, copper loss, or winding loss — is the power dissipated in the transformer when it is delivering current to a connected load. Unlike no load loss, which is constant, on load loss varies dynamically with the load level, increasing as the square of the load current (I²R).

On load loss has three components: I²R loss (copper loss) in the primary and secondary windings, eddy current losses induced within the winding conductors themselves by the leakage magnetic field, and stray loss from leakage flux that intercepts metallic structures such as the tank walls, core clamps, and bushing flanges. The I²R loss is by far the dominant component, proportional to the square of the load current and the DC resistance of the windings. Because winding resistance increases with temperature — copper resistance rises approximately 0.4% per degree Celsius — on load loss is typically specified at a reference temperature of 75°C (IEC) or 85°C (IEEE) to ensure consistent comparison between transformers.

At light loads (0–25% of rated capacity), no load loss dominates the total energy consumption. At moderate to heavy loads (above 50%), on load loss becomes the primary contributor. This interaction is a critical consideration in transformer selection: a transformer that operates most of its life at light load — such as a rural distribution transformer serving a small number of customers — should prioritize low no load loss through the use of an amorphous metal core or high-grade CRGO steel. A transformer that operates consistently near full load — such as an industrial unit powering continuous-process machinery — should prioritize low on load loss through larger conductor cross-sections and copper windings.

Comparison of No Load Loss and On Load Loss

Characteristic

No Load Loss (Core Loss)

On Load Loss (Copper Loss)

When It Occurs

Whenever energized, regardless of load

Only when load current flows

Primary Location

Magnetic core

Windings (primary and secondary)

Main Components

Hysteresis + eddy current + stray

I²R + conductor eddy current + stray

Dependence on Load

None (constant)

Proportional to current squared (I²)

Dependence on Voltage

Proportional to V²

Minimal direct dependence

Temperature Effect

Slight

Significant (~0.4%/°C for copper)

Typical Range (% of rating)

0.2–1.5% of rated kVA

0.5–5% of rated kVA at full load

Key Design Factor

Core material and flux density

Conductor material and cross-section

Dominant At

Light load (0–25%)

Heavy load (above 50%)

How Transformer Losses Are Measured

Both no load loss and on load loss are verified through standardized factory tests defined by IEC 60076-1 and IEEE C57.12.90.

No Load Loss Measurement: The transformer is energized at rated voltage and frequency on one winding (typically the high-voltage side) with the other winding open-circuited. A precision wattmeter measures the input power, which — since no load current flows in the secondary — represents the total no load loss. The excitation current (magnetizing current) is simultaneously measured and should typically be less than 5% of the rated current. Results are corrected to a reference temperature of 20°C.

Load Loss Measurement (Short-Circuit Test): The low-voltage winding is short-circuited, and a reduced voltage is applied to the high-voltage winding — just sufficient to circulate rated full-load current through both windings. Since the applied voltage is only 5–10% of rated, the core flux is negligible and no load loss is essentially zero. All input power measured by the wattmeter therefore represents on load loss. Results are corrected to the standard reference temperature of 75°C or 85°C.

Strategies for Reducing Transformer Losses

Reducing No Load Loss: The most effective strategy is selecting a lower-loss core material. Conventional CRGO (cold-rolled grain-oriented) silicon steel produces no load loss of 0.9–1.3 W/kg at 1.5 T and 50 Hz. Amorphous metal cores reduce this to 0.2–0.4 W/kg — a reduction of 60–75%. Although amorphous cores have a higher initial material cost, the payback period through energy savings is typically 2–5 years, with the remaining 25–30 years of transformer life delivering pure savings. Thinner core laminations, optimized core joint designs, and laser-scribed domain refinement also incrementally reduce losses.

Reducing On Load Loss: The primary lever is conductor material and cross-section. Copper windings have approximately 40% lower resistivity than aluminum, directly reducing I²R loss for the same conductor geometry. Increasing conductor cross-sectional area reduces resistance but increases material cost and physical size. Optimized winding geometry — including transposed conductors to minimize circulating currents and careful attention to skin and proximity effects — reduces conductor eddy current losses. Effective cooling design keeps winding temperatures lower, which reduces resistance and therefore on load loss during operation.

Frequently Asked Questions

What is the difference between no load loss and on load loss in a transformer?

No load loss (core loss) occurs continuously whenever the transformer is energized, regardless of load, and is caused by hysteresis and eddy currents in the magnetic core. On load loss (copper loss) occurs only when load current flows, is caused by I²R heating in the windings, and increases with the square of the load current.

Why does no load loss occur even when nothing is connected to the transformer?

Even with no load, the alternating magnetic flux in the core requires energy to continuously reverse the magnetization of the core steel (hysteresis loss), and the changing flux induces circulating currents within the core material (eddy current loss). Both consume real power that appears as heat.

Which loss is larger — no load loss or on load loss?

It depends on the load level. At light loads (below 25%), no load loss dominates. At moderate to full loads (above 50%), on load loss is larger. For a transformer operating at 100% load, on load loss is typically 3–10 times greater than no load loss.

How can no load loss be reduced?

The most effective method is using amorphous metal core material, which reduces no load loss by 60–75% compared to conventional CRGO silicon steel. Other strategies include thinner core laminations, optimized flux density design, and improved core joint geometry.

How can on load loss be reduced?

Using copper windings instead of aluminum, increasing conductor cross-sectional area, employing transposed conductors to minimize eddy currents, and maintaining effective cooling to keep winding temperatures low all reduce on load loss.

Do transformer losses affect operating cost significantly?

Yes. A 1000 kVA transformer with 1.2 kW no load loss and 6 kW on load loss (at full load) consumes approximately 10,500 kWh per year in no load loss alone — costing over 1,200annuallyat1,200annuallyat0.12/kWh. Over a 30-year service life, the cumulative cost of losses can exceed the initial purchase price of the transformer.

Contact Us
The Group's core businesses cover high-end manufacturing and industrial fields such as chemical products, transformers, and electrical equipment, with transformers and other electrical equipment being the Group's strategic leading industries.

PRODUCTS

QUICK LINKS

CONTACTS

 Tel: +86-18356911563
 Add: Shunhua Road Subdistrict, Lixia District, Jinan City, Shandong Province
 Opening Hours: 
work every day 9:00–18:00
Copyright © 2026 Shandong Future Electric Co., Ltd. All Rights Reserved.
Privacy Policy            Sitemap