| Availability: | |
|---|---|
Rated HV voltage | 10 kV / 12 kV / 35 kV / 40.5 kV (IEC 1 -52 kV) |
Rated LV voltage | 0.4 kV (three-phase, 4/5-wire) or Customized |
Rated capacity | 50–2500 kVA or Customized |
Rated frequency | 50 Hz / 60 Hz (IEC 62271-202 covers up to 60 Hz) |
Transformer type | Oil-immersed/ dry-type |
HV switchgear | Ring main unit (RMU), load switch + current-limiting fuse, vacuum circuit breaker (VCB), or gas-insulated switchgear (GIS/SF6) |
LV switchgear | Moulded-case circuit breakers (MCCB), air circuit breakers (ACB), high-breaking capacity |
Enclosure protection | IP33 / IP44 / IP54 / IP65 |
Ambient temperature | −45 ℃ to +50 ℃ (extreme-cold variants lower) |
Seismic resistance | Horizontal acceleration ≈ 0.4 m/s² |
Noise level | Controllable below 45 dB |
Supply modes | Ring, radial (terminal), dual-source |
Standards | IEC/ASTM/UL/IEEE/GB |
Type | European-style/US-style/Chinese-style/Mobile substation |
Enclosure — outer skin | aluminum alloy / stainless steel |
Enclosure — insulation core | high-density rock wool or polyurethane foam |
Enclosure — inner skin | galvanized steel sheet or fire-resistant panel |
Anti-corrosion coating | Epoxy zinc-rich primer + polyurethane topcoat (double-layer) |
Enclosure fabrication | CNC bending, welding → pickling & phosphating → multi-layer painting |
Transformer core | CRGO Silicon Steel / Amorphous Alloy |
Transformer windings | Copper windings (or aluminum); epoxy cast-resin insulation for dry-type |
Transformer insulation/cooling | Mineral transformer oil / epoxy resin / air |
HV/LV busbars | Copper or aluminum busbar, armored busway |
Switchgear enclosures | Coated steel sheet (e.g., aluzinc/galvanized) |
Foundation / base | Welded steel platform + concrete base |
Urban distribution | Urban network renovation, old-residential upgrading, road lighting, commercial complexes, schools, hospitals, municipal pumping stations |
Rural electrification | Rural grid upgrading, township supply |
Renewable energy | Wind farms , PV plants, distributed storage integration |
EV charging | EV charging-station substations, battery-swap stations |
Industrial & mining | Factories, mines, oil & gas fields, large construction sites |
Temporary & emergency | Site temporary power, emergency rescue, mobile rental units |
Special environments | Severe cold, high altitude, seismic zones, coastal saline areas |
Municipal landscaping | Parks, scenic areas, urban landscape belts |
Metering | Energy meters, current/voltage transformers, metering compartment |
Power factor correction | Automatic low-voltage reactive power compensation (capacitor bank, controller, switching devices) |
DC supply | DC panel (DC 220V / 110V) for control, protection and signaling |
Protection | Relay protection (overcurrent, earth fault, gas, temperature), fuses, surge arresters, interlocking |
Climate control | Anti-condensation heater, intelligent temperature controller, axial fans, temperature/humidity sensors |
Monitoring & communication | Smart monitoring system, remote data acquisition, fault diagnosis, SCADA / telecontrol, IEC 61850 communication |
Lighting | Independent lighting per compartment (explosion-proof optional) |
Ventilation | Natural vents, forced exhaust fans, louvered vents |
Lightning & earthing | Surge arresters, earthing busbar, earth electrodes, earthing grid |
Fire protection | Fire alarm system, extinguishers; oil pit / oil drain for oil-immersed transformers |
Cable & busway | Incoming/outgoing cables, cable terminations, busway/bus duct |
General | Safety locks (anti-misoperation), lifting lugs, nameplate, warning signs, tool kit |